Three-pole Thermal Overload Relays
Three-pole thermal overload relays designed to protect ac circuits against overloads, phase failure, long starting times and prolonged stalling of the motor.
Adjustable relay setting dial
Test button
Stop button
Manual/auto reset
Trip indicator
Sealable cover
1N/O & 1N/C auxiliary contacts
Direct mounting beneath three-pole contactors or independent mounting on DIN rail
Insulation voltage 600V, Withstand Voltage 6kV.
RANGE |
TeSys
|
|
PRODUCT NAME |
TeSys LRD
|
|
PRODUCT OR COMPONENT TYPE |
Differential thermal overload relay
|
|
DEVICE SHORT NAME |
LRD
|
|
RELAY APPLICATION |
Motor protection
|
|
PRODUCT COMPATIBILITY |
LC1D18 LC1D25 LC1D32 LC1D12 LC1D09 LC1D38
|
|
NETWORK TYPE |
DC AC
|
|
THERMAL OVERLOAD CLASS |
Class 10A IEC 60947-4-1
|
|
THERMAL PROTECTION ADJUSTMENT RANGE |
5.5…8 A
|
|
[UI] RATED INSULATION VOLTAGE |
Power circuit 600 V CSA Power circuit 600 V UL Power circuit 690 V IEC 60947-4-1
|